Page 3 pre installation considerations before proceeding with the sleeve installation ensure the following guidelines for locating the wall opening and sleeve are met.
Ptac wall sleeve installation instructions.
This information might be about you your preferences or your device and is mostly used to make the site work as you expect it to.
See the drain kit for internal actual installation instructions.
The sleeve will fit flush in the wall extending outside the structure.
Wall sleeve installation 920 087 04 8 05 wall sleeve installation instructions pdxws note.
All wall and window wall installations must provide for proper drainage.
Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve chassis and accessories.
Prepare and install the new wall sleeve according to the instructions below.
The wall sleeve be installed a minimum of 36 from the ceiling.
For sunrooms and modular buildings adhere to their installation instructions for supporting and sealing sleeve to their frames.
To ensure proper airflow and filter removal it is recom mended installation of the wall sleeve be a minimum of 36 from the ceiling.
In applications where the drain holes on the ptac wall sleeve are not exposed beyond the wall an internal drain system is recommended.
The air conditioner will slide into the sleeve but is not flush with the wall.
For new installs ensure the wall is properly framed to support the weight and dimensions of the wall sleeve and air conditioner.
Installation guidelines for sealing ptac sleeves read these instructions completely before starting any installation.
Inches mm inches mm inches mm wall sleeve only 3 75 0 0 0 0 subbase kit 3 75 3 1 4 85 2 3 4 70.
There is a portion of the air conditioner which extends a few inches back into the room.
Standard steel wall cases are 42 w 16 h 13 3 4 d.
While the dimensions may appear to be incompatible the 2 devices should fit properly.
16 24 28 and 31 deep cases are available for thicker walls.
If the sleeve projects more than 8 into the room a sub base or other means of support must be used.
In applications where the drain holes on the ptac wall sleeve are not exposed beyond the wall an internal drain system is recommended.
The wall sleeve must be fastened securely before installing the air conditioner unit.
All wall and window wall installations must provide for proper drainage.
For sunrooms and modular buildings adhere to their installation instructions for supporting and sealing sleeve to their frames.
When you visit any website it may store or retrieve information on your browser mostly in the form of cookies.
Tools required by.
Failure to install and maintain our product according to these instructions may void any product warranty.
Wall case should be sealed caulked to the inside wall on all four 4 sides.
Wall case must be sealed caulked to outside wall on all four 4 sides.